Connection example 2: Leakage-sensor connected to MultiSensor
Plug the connection cable of the leakage-sensor into one of the jacks of the Kentix Power-Adapter (KIO1).
Connect the MultiSensor to the Power-Adapter with the modular cable (sent with the Power-Adapter).
Connect the delivered power supply to the Power-Adapter for currency.
The powering of leakage-sensor and MultiSensor is realized via the Power-Adapter, the alarming via the
external input of the MultiSensor.
With the ControlCenter enter a suitable name for the external alarm input and set the alarming of the input to
„Always-Active“ for a permanent alarming. If the leakage sensor is working with opening the contact on an
alarm, additionally change the alarm logic to „Open“.
MultiSensor-RF/LAN
Leakage-Sensor
KENTIX Power-Adapter
KENTIX System-jack
NOTE!
Using the leakage sensor together with a MultiSensor a fully wired patch cable is required for the
connection between MultiSensor and power adapter.